Articles about architecture, engineering, city planning, software, construction and other fun stuff. Put together by architects at EVstudio in Denver Colorado.

Don't Make Your Solid Blocking Too Solid – Attic Ventilation Requirements

I was at a job site today and noticed that the contractor had used blocking between trusses where the blocking was large enough that it actually blocked off the ventilation from the soffits.  They're going to have to go back and put holes in the blocking to meet the ventilation requirements.

Therefore it seems like a good time to review the ventilation requirements in the International Building Code.

First off, you need at least 1" of airspace between the insulation and the roof sheathing. The venting must have a total area of at least 1/150 of the ventilated area and at least half that area must be in the upper portion located at least 3' above the cornice or eave vents. So where you have a 3,000 sf attic you'd need 20 sf of venting with at least 10 sf of that in the upper portion of the roof.

The International Residential Code states that no more than 80% of your venting can be in the upper portion of the roof, the IBC does not have this requirement.

Where you have a vapor retarder with a transmission rate less than 1 perm on the warm side of the insulation you can reduce the venting area requirements by 50% to 1/300.

Finally remember that openings for ventilation need to be covered with material that has a minimum 1/8" openings and a maximum 1/4" openings.

Related Articles:
  1. Temperature Control in Buildings – What is the Minimum Heat Level Required in the Building Code?
  2. Opening Protection and Fire Rating in Garages – Requirements for the Door and Gypsum Board
  3. Attic Access in Houses
  4. Windows Close to the Floor

Tagged as: , , ,

Leave a Response


EVstudio Architect Engineer & Planner Online Magazine
Denver & Evergreen Colorado, Copperas Cove Texas
Yes, we take outside article submissions.